Keeping exit routes and exit signs compliant under OSHA
A walk-round checklist built from 29 CFR 1910.36 and 1910.37 — unlocked exit doors, clear routes, lit and legible EXIT signs, and keeping exits open during repairs — for the person who maintains the building.
- Where it applies
- United States (federal OSHA)
- Checked against its sources
- 7 November 2026
Exit routes are designed into a building once, by an architect, and then kept working every day by whoever maintains it. Most of what goes wrong is not design: it is a chained door, a stack of chairs in a corridor, a dead EXIT sign, or a fire door wedged open. OSHA’s two exit-route standards — 29 CFR 1910.36 on design and 29 CFR 1910.37 on maintenance — read almost like a checklist for that daily work. This guide turns them into one.
Who this applies to
OSHA’s standards protect employees. Private schools, churches and other non-profits with employees are generally covered, by federal OSHA or by a state’s plan. Public schools and local governments are covered only in states that run an OSHA-approved State Plan; elsewhere, OSHA’s State Plans page notes, “state and local government workers are not covered by federal OSHA.” Separately, your state or local fire code will have its own requirements for exits, which the local fire official enforces. The checks below are a sound baseline under either.
Exit doors
Openable from the inside, always
1910.36(d)(1) is the requirement most often broken in buildings that worry about security: “Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge.” A panic bar that locks only from the outside is permitted on exit discharge doors.
Paragraph (d)(2) adds that exit route doors must be “free of any device or alarm that could restrict emergency use of the exit route if the device or alarm fails.” An alarmed door is allowed; a door that stays locked when its alarm or maglock loses power is not.
Check: every exit door opens from inside with one movement, no padlocks or chains are on it during occupied hours, and powered locks release when they should.
Swing and hinges
A side-hinged door must connect any room to an exit route (e)(1). The door must swing out in the direction of travel if the room is designed for more than 50 people or is a high hazard area (e)(2). Assembly halls, gyms and sanctuaries are the rooms to look at.
Fire doors into an exit
Where an opening leads into an exit — a stair enclosure, for example — it must be protected by “a self-closing fire door that remains closed or automatically closes in an emergency upon the sounding of a fire alarm or employee alarm system” (a)(3).
Check: fire doors close fully on their own and latch; nothing props them open unless it is a hold-open device that releases on the alarm.
The route itself
1910.37(a)(3) requires exit routes to be “free and unobstructed. No materials or equipment may be placed, either permanently or temporarily, within the exit route.” The access to an exit may not pass through a room that can be locked, such as a bathroom, or lead into a dead-end corridor.
Two figures from 1910.36(g) give the minimums: an exit access must be at least 28 inches wide at all points, and the ceiling at least 7 feet 6 inches high, with nothing projecting below 6 feet 8 inches. Objects that project into the route must not narrow it below the minimum width (g)(4).
Exit routes must also be kept free of “explosive or highly flammable furnishings or other decorations” (37(a)(1)). Seasonal decorations along corridors are worth a second look.
Check: corridors and stairs are clear, nothing is stored in them “for now”, and decorations are not on or around exit doors.
Signs and lighting
1910.37(b) is specific:
- Each exit route must be lit well enough that an employee with normal vision can see along it (b)(1).
- Each exit must be clearly visible and marked by a sign reading “Exit” (b)(2).
- Exit doors must be free of decorations or signs that obscure them (b)(3).
- Where the way to an exit is not obvious, signs along the route must point to the nearest exit, and the line of sight to an exit sign must be clear at all times (b)(4).
- Any door or passage that could be mistaken for an exit must be marked “Not an Exit” or with its actual use, such as “Closet” (b)(5).
- Each exit sign must be illuminated to at least five foot-candles (54 lux) by a reliable light source and be distinctive in color; self-luminous or electroluminescent signs need a surface value of at least 0.06 footlamberts (0.21 cd/m²) (b)(6).
- The word “Exit” must be in letters at least six inches high, with strokes at least three-fourths of an inch wide (b)(7).
Check: every EXIT sign is lit — including on its battery, if it has one — readable, and visible from the route; directional signs are where a stranger would need them; storerooms and closets that look like exits are labelled.
OSHA’s rule says safeguards such as “sprinkler systems, alarm systems, fire doors, exit lighting must be in proper working order at all times” (37(a)(4)), but it does not set a testing interval for emergency lighting. Your adopted fire code is where that interval comes from; ask your local fire official which one applies.
During repairs and building work
1910.37(d)(2) matters for anyone planning summer works in a school or a renovation in a church: during repairs or alterations, employees must not occupy a workplace “unless the exit routes required by this subpart are available and existing fire protections are maintained, or until alternate fire protection is furnished that provides an equivalent level of safety.”
Check before work starts: which exits the contractor will block, how long for, and what replaces them. Put it in the contract.
The alarm and the plan
1910.37(e) requires an operable employee alarm system with a distinctive signal, unless employees can see or smell a fire in time to be warned. Where another OSHA standard requires an emergency action plan, 1910.38 says it must be in writing and available to employees — though an employer with 10 or fewer employees may communicate it orally — and must include evacuation procedures and exit route assignments.
Turning it into a routine
None of this needs specialist equipment. A monthly walk of every route, with the checks above as a list, catches almost everything:
- Open each exit door from inside.
- Walk each route and look for anything stored in it.
- Look at every EXIT sign and directional sign; press the test button on battery units.
- Close each fire door and watch it latch.
Record the date, who walked it, and each problem found as its own repair job so it is fixed rather than noted. In Sitekeep, the walk can be a monthly preventive maintenance schedule with a checklist, and anyone in the building can report a dead sign or a blocked door from a QR code without an account.
Sources
- 29 CFR 1910.36, Design and construction requirements for exit routes, OSHA — doors, swing, width and height.
- 29 CFR 1910.37, Maintenance, safeguards, and operational features for exit routes, OSHA — obstructions, signs, lighting, repairs and alarms.
- 29 CFR 1910.38, Emergency action plans, OSHA.
- State Plans, OSHA — who federal OSHA does not cover.
This guide explains what the law and the regulator say; it is not legal advice. Where a figure matters to your building, read the source it links to and your own risk assessment.