Fire extinguisher inspections under OSHA — monthly, annual and hydrostatic
What 29 CFR 1910.157 requires for portable fire extinguishers — the monthly visual inspection, the annual maintenance check, the six-year and hydrostatic intervals — and whether it applies to your school, church or town.
- Where it applies
- United States (federal OSHA)
- Checked against its sources
- 7 November 2026
Every portable fire extinguisher in a US workplace has three clocks running on it: a monthly look, an annual maintenance check, and a test of the cylinder itself every five or twelve years. The federal rule is 29 CFR 1910.157, and it is short enough to read in full. This guide walks through what it asks of the person looking after the building — and starts with the question of whether it applies to you at all.
First: does federal OSHA cover you?
OSHA’s standards protect employees. Two things follow for the organisations this guide is for:
- Private schools, churches and other non-profits with employees are generally covered by federal OSHA, or by their state’s plan if the state runs one for private employers.
- Public schools and local governments are not covered by federal OSHA. OSHA’s State Plans page explains that in states without a State Plan, “state and local government workers are not covered by federal OSHA.” In the 29 states and territories that do run a plan — 22 covering private and public workers, and seven covering public workers only — the state’s rules apply, and they must be “at least as effective as OSHA.”
Even where OSHA does not reach you, the fire code your state or locality has adopted may set its own extinguisher requirements, and your fire marshal or other local fire official enforces it. The OSHA intervals below are a sound baseline either way, but ask your local fire official which code applies to your building.
Do you have to provide extinguishers at all?
Not always. Under 1910.157(b)(1), an employer whose written fire safety policy requires the immediate and total evacuation of employees when the alarm sounds — with an emergency action plan and fire prevention plan meeting 1910.38 and 1910.39 — and who has no extinguishers in the workplace, is exempt from the section, unless another standard requires an extinguisher.
Most buildings do have extinguishers. Once they are there and meant for employee use, the rest of the section applies.
Where they go
Paragraph (d) sets travel distances. For ordinary combustibles (Class A), employees must be within 75 feet of an extinguisher. For flammable liquids (Class B), the distance from the hazard area is 50 feet or less. Class C extinguishers follow the pattern for the Class A or B hazards nearby. Extinguishers must be mounted, located and identified so they are “readily accessible to employees without subjecting the employees to possible injury” (paragraph (c)(1)).
A school kitchen, a boiler room, a grounds workshop with fuel cans and a church kitchen used for suppers are the places to check distances first.
The three clocks
| How often | What the rule requires | Paragraph |
|---|---|---|
| Monthly | A visual inspection of every portable extinguisher | (e)(2) |
| Annually | A maintenance check, with the date recorded | (e)(3) |
| Every 6 years | Stored-pressure dry chemical units that need a 12-year hydrostatic test are emptied and maintained | (e)(4) |
| Every 5 or 12 years | A hydrostatic test of the cylinder, by type, per Table L-1 | (f)(2) |
Monthly: the visual inspection
1910.157(e)(2) says portable extinguishers “shall be visually inspected monthly.” The rule does not list what to look at, but paragraph (c)(4) gives the test the inspection is for: extinguishers must be “maintained in a fully charged and operable condition and kept in their designated places at all times except during use.” In practice a monthly walk checks that each one is:
- in its place, visible and not blocked;
- showing a full charge on its gauge, where it has one;
- undamaged, with the pin and tamper seal intact and the hose clear.
It takes a minute per extinguisher. Most people initial and date the tag on the unit; a list by location does the same job and is easier to check.
Annually: the maintenance check
Under (e)(3), each extinguisher gets “an annual maintenance check.” Stored-pressure extinguishers do not need an internal examination. You must record the annual maintenance date and keep that record “for one year after the last entry or the life of the shell, whichever is less”, available to OSHA on request. Most organisations have a fire protection contractor do the annual check and tag each unit.
Every six years, and the hydrostatic test
Stored-pressure dry chemical extinguishers that require a 12-year hydrostatic test must be emptied and given the applicable maintenance every six years (e)(4). Disposable, non-refillable units are exempt, and the six years restart from any recharge or hydrostatic test.
The hydrostatic test itself — pressure testing the shell — follows Table L-1 in the standard. Water, foam, AFFF, carbon dioxide and stainless-steel dry chemical extinguishers are tested every 5 years; dry chemical units with mild steel, brazed brass or aluminum shells, and Halon units, every 12 years. The test must be done by trained persons with suitable equipment (f)(1), and you must keep a certification record with the date, the tester’s signature and the extinguisher’s serial number or other identifier (f)(16), until the next test or until the unit leaves service.
A unit also needs a hydrostatic test whenever it shows new corrosion or mechanical damage (f)(4).
While one is away
When an extinguisher goes out for maintenance or recharging, (e)(5) requires “alternate equivalent protection.” Ask your contractor to swap units rather than take them away, or to bring loaners.
Training
Where extinguishers are provided for employee use, (g) requires an education program on their use and the hazards of fighting an incipient fire — at first employment and at least annually after that. Employees designated to use firefighting equipment under an emergency action plan need training on that equipment, again at least annually.
Making it stick
The monthly inspection is the one that lapses. A few habits keep it going:
- Keep a list of every extinguisher by building and room, with its type and its last hydrostatic test date, so the 5- and 12-year tests do not surprise you.
- Put the monthly walk on a fixed day and make it somebody’s job by name.
- When a monthly check finds a problem — a low gauge, a missing pin — record it as a repair with a due date, not just a note on the tag.
In Sitekeep, each extinguisher can be an asset with its location, a monthly preventive maintenance schedule makes the inspection a work order when it falls due, and a QR label on the unit lets anyone report a problem with it from a phone.
Sources
- 29 CFR 1910.157, Portable fire extinguishers, OSHA — every requirement quoted above, including Table L-1.
- State Plans, OSHA — which states run their own plans and who federal OSHA does not cover.
This guide explains what the law and the regulator say; it is not legal advice. Where a figure matters to your building, read the source it links to and your own risk assessment.