The monthly sentinel outlet checks, the temperatures HSE says to look for, the weekly flushing of little-used outlets, and the records to keep — for a school, church or council building.

Where it applies
Great Britain
Checked against its sources
7 November 2026

Legionella bacteria live in ordinary hot and cold water systems, and they multiply when water sits at the wrong temperature. For most small sites the control is not chemistry or contractors: it is a routine of temperature checks and flushing that one person can run, written down. This guide sets out that routine as the Health and Safety Executive (HSE) describes it.

Whose duty it is

HSE’s leaflet for dutyholders, Legionnaires’ disease: a brief guide for dutyholders (INDG458), says that as an employer or a person in control of premises you “have health and safety duties and need to take suitable precautions to prevent or control the risk of exposure to legionella.” The full legal detail is in HSE’s Approved Code of Practice, Legionnaires’ disease: the control of legionella bacteria in water systems (L8).

The duty starts with a risk assessment. INDG458 says there is a reasonably foreseeable risk if, among other things, water is stored or re-circulated, some of it sits between 20 and 45 °C, there is rust, sludge or scale for bacteria to feed on, and spray or droplets can be produced — showers being the obvious example. You may be competent to carry out the assessment yourself; if not, you should get someone who is.

You must also appoint a competent person to manage the risk. That can be you, a colleague, an outside company, or a combination — but if several people share it, the leaflet asks that everyone knows what they are responsible for.

The temperatures that matter

HSE’s page on hot and cold water systems gives the figures a routine is built around:

Where What HSE says to look for
Cold water sentinel outlets Below 20 °C after running for 2 minutes
Hot water sentinel outlets At least 50 °C within 1 minute of running
Hot water leaving the cylinder/calorifier At least 60 °C
Hot water supply to a mixing valve (TMV) At least 50 °C within 1 minute of running
Cold water storage tank Below 20 °C, checked at the ball valve outlet every 6 months

The logic is simple: legionella grows in the band between those numbers, so cold water should stay cold and hot water should stay hot all the way to the tap.

Sentinel outlets, and why they are the heart of it

A sentinel outlet is a tap chosen because it tells you about the whole run of pipe. HSE’s technical guidance, HSG274 Part 2, says that in a simple system these are typically the taps furthest from and nearest to the hot water heater, or to the cold water tank, with the ends of long branches added as further sentinels. In a circulating hot water system the far sentinels are the return legs towards the end of each loop. If the furthest tap reaches temperature in time, the pipe between is doing its job.

HSE’s routine is to check the temperature at sentinel outlets monthly, and to check other representative outlets “on a rotational basis” so that, over time, the whole system is covered. The choice of outlets should come out of your risk assessment, which is one reason to have the assessment done before the routine starts.

To take a reading, run the tap and measure the water with a thermometer in the flow, or a surface probe on the pipe, at the 1-minute mark for hot and the 2-minute mark for cold. HSE has short videos showing each check, linked from the same page.

Little-used outlets: flush them weekly

Stagnant water is the other half of the risk. HSE’s guidance is that for “infrequently used outlets, instigate a programme of regular flushing (weekly)”, flushing through and purging to drain “without release of aerosols”.

This is the check that schools and churches most often need to think about, because so much of the building stands empty for long stretches:

  • the shower in a sports changing room that is used only in one season;
  • the tap in a vestry or side room used once a week, or less;
  • every outlet in the building after the summer holiday.

A practical approach is to keep a list of these outlets, with a column for each week. Run each one long enough to draw fresh water through, gently so it does not spray, and tick it off. Where an outlet is never used at all, the HSE page’s advice on removing dead legs and redundant pipework is the permanent fix and worth raising with whoever maintains your plumbing.

The less frequent checks

The same HSE page lists the other routine items:

  • Showerheads and hoses: dismantle, clean and descale them quarterly, or as your risk assessment decides.
  • Cold water storage tanks: check the tank is clean, with a tight-fitting lid, at least annually; and check the water temperature at the ball valve every six months.
  • Hot water cylinders: a visual check for scale and sludge when possible, and a check that the cylinder stays clean, at least annually.

What to keep, and for how long

INDG458 sets out the records. If you have five or more employees you must record the significant findings of your assessment. Records should cover who is responsible, the significant findings, the written control scheme and how it is carried out, and “the results of any inspection, test or check carried out, and the dates”, including whether the system was in use at the time.

On retention, the leaflet says records “should be retained throughout the period for which they remain current and for at least two years after that period”, and that the results of checks “should be retained for at least five years.”

Five years of monthly temperature readings is a lot of paper. Whatever you keep it in, each entry needs the outlet, the date, the reading, who took it, and what was done if the reading was out of range. In Sitekeep, each sentinel outlet can be an asset with a monthly schedule, so the check arrives as a work order and the completed ones stay in that outlet’s history.

When a reading is out of range

A single low hot-water reading is a fault to find, not a reason for alarm. Typical causes are a cylinder thermostat set too low, a failed circulation pump, or a mixing valve fitted too far from the tap — HSE notes that pipe runs downstream of a thermostatic mixing valve should not exceed 2 m. Record the reading, report it to whoever maintains the system, and recheck after the fix. If readings keep failing, review the risk assessment with your competent person.

Other duties to know about

INDG458 also notes that a site with a cooling tower or evaporative condenser must notify its local authority in writing; few schools or churches have one. And a case of legionellosis in an employee who worked on a water system likely to be contaminated is reportable under RIDDOR.

Sources

This guide explains what the law and the regulator say; it is not legal advice. Where a figure matters to your building, read the source it links to and your own risk assessment.